LBRE - Load Bank Rental Europe
Home/Products/Avtron 8400 Container Load Bank
Avtron 8400 Container Load Bank

Avtron 8400 Container Load Bank

The Avtron 8400 is a 20 foot ISO containerized resistive/reactive load bank with capacities up to 6250 kVA depending on voltage. Equipped with SIGMA control enabling multiple options for testing, networking and data acquisition. The resistive load is located in the top of the container and the inductive in the bottom. Ideal for testing generators, UPS systems, and power sources in outdoor environments.

Key Specifications

Capacity: Up to 6250 kVA
Voltage: 400V/480V, 3-phase
Frequency: 50/60 Hz
Cooling: Forced air with vertical discharge, four axial metal-bladed aerofoil fans
Request a Quote

Full Specifications

Standard Capacity
Up to 6250 kVA
Resistive Capacity
Up to 5000 kW
Reactive Capacity
Variable kVAR
Load Step Resolution
1 kW, 5 kVAR
Voltage Rating
400V @ 50Hz (5000 kVA), 480V @ 60Hz (6250 kVA)
Control System
SIGMA Control
Hot Air Discharge
Vertical
Construction
20ft ISO style container with carbon steel structure
Cooling System
Forced-air cooling by axial metal-bladed aerofoil fans
Fan Quantity
Four fans
Resistor Elements
Non-finned sheathed stainless steel elements
Element Rating
Continuously rated to operate at up to 800°C
Load Tolerance
Resistive: Within 2½% of total capacity, Inductive: Within 3% of total capacity
Ambient Temperature
Rated at 35°C (50°C rating available)
Humidity
Up to 90% RH, non-condensing
Cable Entry
Two gland plate side access points (450 × 280mm) with additional plate under floor (963 × 250mm)

Features

  • 20ft ISO containerized design for outdoor installation
  • Combined resistive and reactive load testing capabilities
  • SIGMA control system for precise load management at any power factor
  • Vertical hot air discharge for safe operation
  • Walk-in control room with full access to control and switchgear cabinets
  • Electrically operated automatic side and end louvers
  • High-quality stainless steel resistive elements rated up to 800°C
  • Three-phase inductors with thermal protection
  • Internal lighting and power outlets for maintenance
  • Anti-condensation heaters in control cabinets

Applications

Generator Testing

Verify performance and stability of generators under various load conditions and power factors

Data Center Power Testing

Test and validate data center power systems including UPS and backup generators with realistic loads

Power Plant Commissioning

Load testing during commissioning of power generation facilities with both resistive and reactive loads

Power Factor Testing

Simulate various power factor conditions to test generator and power system performance

Interested in this product?

Contact us today to discuss your requirements and get a quote.

Contact Us